The static performance test measures the heat transfer capacity,temperature/flow control accuracy and the energy consumption efficiency of the pump unit of the CDU under rated conditions to verify whether it meets the design specifications and hits the energy-efficiency targets.

Test Background
The heat transfer efficiency, control accuracy and pump unit efficiency of the CDU under steady-state conditions determine the basic performance of the liquid cooling system, which directly affects the temperature stability of the chip and the system energy consumption.
Test Introduction
The static performance test measures the heat transfer capacity, temperature/flow control accuracy and the energy consumption efficiency of the pump unit of the CDU under rated conditions to verify whether it meets the design specifications and hits the energy-efficiency targets.
Testing Objectives
Verify the heat exchange capacity of the heat exchanger under rated conditions
Evaluate the steady-state error of temperature and flow control
Measure the efficiency curves of the pump unit at different rotational speeds
Provide basic data for system energy efficiency optimization
Test Standards
T/CESA 1249.3-2023 Technical specification for cooling capacity distribution units
OCP CDU Performance Test Guide
ASHRAE Energy Efficiency Test Method for Liquid Cooling Systems
Applicable Products/Related Fields
Suitable for the selection and acceptance, R&D optimization, and energy-saving renovation evaluation of CDU in liquid-cooled data centers.
Test Content
Heat transfer efficiency test: Calculate the heat transfer amount by the enthalpy difference method on the primary/secondary side
Control accuracy test: The deviation between the set value and the actual value is ≤ ±0.5°C/±3%
Pump unit efficiency test: Power consumption and head curves at different flow rates
Static power consumption test: Energy consumption in standby mode
Project Advantages
High-precision sensor system (temperature ±0.1℃, flow rate ±0.5%)
Supports automatic testing at multiple operating points
Provides energy efficiency rating and optimization suggestions
Laboratory Configuration
Enthalpy difference method heat exchange test platform (150kW at maximum)
High-precision temperature/pressure/flow sensors
Power analyzer
Automated data acquisition system
FAQ
Q: What's the difference between the heat exchange efficiency and COP of CDU?
A: The heat exchange efficiency refers to the heat exchange capacity of the heat exchanger, and COP is the energy efficiency ratio (heat exchange/ power consumption). Both jointly determine the performance of CDU.