The safety test covers pressure resistance test, electrical safety test, leakage protection test and sealing test, comprehensively verifying the safety performance of the liquid-cooled pump under rated working conditions and abnormal conditions.

Test Background
As the power core of the CDU and the liquid-cooling system, the electrical safety, pressure-resistance ability and sealing performance of the liquid-cooling pump are directly related to the safe operation of the system. Once it fails, it may lead to system shutdown or leakage.
Test Introduction
The safety test covers pressure resistance test, electrical safety test, leakage protection test and sealing test, comprehensively verifying the safety performance of the liquid-cooled pump under rated working conditions and abnormal conditions.
Testing Objectives
Verify the structural strength of the pump body under 1.5 times the working pressure
Ensure the reliability of electrical insulation and grounding protection
Detect the leakage risk of the pump body and its connections
Verify the response reliability of the leakage protection device
Test Standards
T/CESA 1249.3-2023 CDU technical specification (pump part)
GB/T 1032 Test methods for three-phase asynchronous motors
EN/UL 62368-1 Electrical safety requirements
ISO 19879 Sealing test of hydraulic components
Applicable Products/Fields
Suitable for CDU circulating pumps, secondary-side pumps, primary-side pumps, variable-frequency pumps, etc.
Test Content
Pressure resistance test: Maintain the pressure at 1.5 times the working pressure for 30 minutes
Electrical safety test: Insulation resistance ≥ 100 MΩ, withstand voltage 1500 V
Leakage protection test: Automatic shutdown response when simulating leakage
Sealing test: Measurement of static/dynamic leakage rate
Project Advantages
Comprehensive electrical and hydraulic safety test capabilities
Capable of simulating multiple fault modes
Provides safety margin evaluation and certification support
Laboratory Configuration
Hydrostatic test bench
Safety comprehensive analyzer
Leakage simulation test platform
Helium mass spectrometry leak detector
FAQ
Q: What is the protection level requirement for the liquid-cooled pump? A: Usually, it is required to be above IP54 to ensure dust and splash-proof. For outdoor applications, IP65/IP67 is required.